|
INFORMATION, DUCTING
|
Whichever way you intend to hook up the ducting, make sure to have a heating contractor do the work. He will know all the safe procedures necessary to keep you and your family safe. Also, make sure that you take into account that the first 10 feet of hot air ducting MUST be insulated from any wood.
Reasonable air flow and heat delivery requires certain planning that must be done for your particular application. Each house is unique and so is its ducting system. That's another reason for having a local heating contractor do this work. Even if we would try to give guidance over the phone, it would ONLY be general, and might not apply because of unique aspects of YOUR house.
Elbows and angle fittings in both directions are standard available items for the size ducting that JUCAs feed.
This allows the JUCA and the other furnace to be totally independent
of each other but generally requires one of our optional blowers (to
duplicate the air circulation capability of the other furnace blower.
Join the existing system at or near its thickest section (probably
near the other furnace). A check-flow damper may need to be installed
(See Check-Flow Damper) to eliminate
back flow through either furnace whenever the other one is operating.
Of course, it must not stop warm air that is trying to leave either
furnace (for example, if BOTH try to operate at the same time),
and only keep air from going backward into either.This connection method involves considering installing air filters and a humidifier in the JUCA air path, because its air does NOT go through those features of the other furnace. JUCAs are compatible with ALL standard air filters and humidifiers.
This "alternate" type of connection is a little more complicated than it first seems even though it is a way recommended by some of our competitors (we think, incorrectly). The ONLY appropriate ways to do this involve EITHER getting the JUCA blower that is about the same size and capacity as the blower in the other furnace (so it can't be over-powered) OR to design the connecting point to have a "venturi effect" as mentioned above. If this is done correctly, the air flow of the other (big) blower, is capable of causing a "sucking" action to actually help pull the JUCA's warm air out into its path.
If you do use this method, you should check the JUCA's hood temperature when operating. If it is hotter than allowing you to hold your hand against it, then probably the air is not being able to leave the stove properly and some change in the connection area is necessary.
The two furnace blowers work in "series" in this installation. The
JUCA heats the air then sends it to the other furnace where it is
mixed with some unheated air then pushed through without its burners
being on. You use the other furnace blower to do the bulk of the
work of circulating throughout the house, but the JUCA blower is
still necessary to get the heated air to the other furnace blower.
It is very important to make sure that the JUCAs heated air cannot
overheat anything. Study every place that hot air could wind up,
even backwards in the ducting system.When the JUCA is operating, the air in the cold air return duct is drawn into the JUCA, heated up there, and then put back into that same cold air return duct (after the BAFFLE shown). Then the JUCA-warmed air proceeds to and through the other furnace's blower, on its way to the house ducts. ONLY the blower of the conventional furnace operates (NOT the burner, so no fuel is used). That (large) blower does most of the work of distributing the JUCA-warmed air throughout the house.
This configuration still requires at least the standard blower to operate on the JUCA. The other furnace's blower is not designed to "suck" the air through the JUCA, as that would cause something bad called "cavitation."
When the JUCA is NOT operating, the conventional furnace pulls MOST of its air by its original path, past the BAFFLE, and pulls the remainder through the JUCA heat exchanger path. The conventional furnace operates normally.
It would also be possible to make the BAFFLE motorized. Then, the cold air return duct would remain totally unobstructed for the normal operation of the conventional furnace, and the BAFFLE would swing out and divert most of the air through the JUCA air path when the JUCA blower turns on. The motor of that damper would just be wired in parallel with the JUCA blower, so it would turn on and close at the correct times.
This general arrangement's air path ALWAYS passes through the conventional furnace's air filter system and humidifier.
Sometimes, in houses that currently don't have ducts, people operate the JUCA for one winter, to see how much of the house can be heated to the comfort level desired, without ducting. If the results are satisfactory, then nothing else would ever need to be done. But, if it was found that a single distant bedroom or bathroom was not warm enough, it would be possible to run one small duct the following year, to get some extra heat to that area. JUCAs are amazingly flexible in such ways!
It would even be possible to automate this kind of installation with a Relay as described below.
The following describes a "NON-invasive" method of connection that does NOT involve doing anything inside the other furnace. The SPST relay would be used. The coil of this relay would be wired in parallel with the JUCA's blower motor, so the relay would be actuated whenever the JUCA blower was on.
The SPST switch contacts would be wired in parallel with the 24-volt circuit SUMMER FAN switch in the sub-base of the conventional furnace's wall thermostat. The effect would be so that the SUMMER FAN circuit would be automatically closed, just as if you manually moved that switch on the sub-base. This method does NOT invade the other furnace, so it does not affect any warranties or anything!
MAKE ABSOLUTELY SURE THAT ALL OF THE FIRST 10 FEET OF WARM AIR DUCTING FROM THE JUCA IS INSULATED FROM ANY WOOD OR OTHER COMBUSTIBLES, EVEN IF IT MEANS MODIFYING EXISTING DUCTWORK.
If the JUCA is installed in an unheated space, then a cold air return MUST be provided for the JUCA. There are a LOT of good reasons for this. Trust us!
If ducts pass through an unheated basement or crawlspace, they should be insulated with Fiberglas insulation, to minimize heat loss in those ducts, just like with any other furnace.
It is extremely important to measure the "Static Pressure Levels" and air flow rates. Otherwise, any or all of several problems could occur.
465 cfm |
915 cfm |
1240 cfm |
1460 cfm |
2000 cfm |
2550 cfm |
|
St'd |
Med |
Mid |
Lrg |
1/2 |
3/4 |
|
Electric |
115watt |
5.8 amp |
3.8 amp |
3.8 amp |
7.1 amp |
9.5 amp |
HP |
1/20 |
1/6 |
1/4 |
1/4 |
1/2 |
3/4 |
RPM |
1530 |
1050 |
1050 |
1050 |
1050 |
1050 |
WC |
Cubic Feet per Minute |
|||||
0.0 |
465 |
- |
- |
- |
- |
- |
0.10 |
428 |
- |
- |
- |
- |
- |
0.20 |
396 |
- |
- |
- |
- |
- |
0.30 |
352 |
992 |
- |
1460 |
- |
- |
0.40 |
305 |
961 |
1240 |
1430 |
- |
- |
0.50 |
227 |
915 |
1210 |
1385 |
2000 |
- |
0.60 |
120 |
864 |
1175 |
1320 |
1960 |
- |
0.70 |
40 |
726 |
1120 |
1220 |
1900 |
- |
0.80 |
- | 513 |
1030 |
- |
1840 |
2550 |
0.90 |
- | - | 910 |
- |
1765 |
2460 |
1.00 |
- | - | - | - | 1670 |
2340 |
1.10 |
- | - | - | - | 1540 |
2150 |
1.20 |
- | - | - | - | 1140 |
1860 |